Oshan One Way Cassette Type (CO) Fan Coil
Specification |
|
|
Model |
|
SV 300 |
SV 400 |
SV 600 |
|
|
Air
Flow |
H |
M3/hr(CFM) |
510 (300) |
680 (400) |
1020 (600) |
|
|
M |
416 (245) |
535 (315) |
860 (506) |
|
|
L |
306 (180) |
346 (203) |
642 (378) |
|
|
Cooling Capacity |
Total |
H |
kW |
3.51 |
5.05 |
6.74 |
|
|
M |
2.97 |
4.24 |
6.22 |
|
|
L |
2.25 |
2.97 |
5.16 |
|
|
Sensible |
H |
kW |
2.53 |
3.56 |
4.9 |
|
|
M |
2.15 |
2.94 |
4.4 |
|
|
L |
1.64 |
2 |
3.58 |
|
|
Cooling Water Flow |
L/min |
9.8 |
14.4 |
19.3 |
|
|
Cooling Water Pressure Drop |
kPa |
8.37 |
21.52 |
29.6 |
|
|
Heating Capacity |
H |
kW |
3.67 |
5.06 |
7.25 |
|
|
M |
3.12 |
4.18 |
6.37 |
|
|
L |
2.42 |
2.89 |
5.07 |
|
|
Heating Water Flow |
L/min |
5.34 |
7.38 |
10.6 |
|
|
Heating Water Pressure Drop |
kPa |
2.09 |
5.38 |
11.66 |
|
|
Fan |
Type |
Forward / Centrifugal |
|
|
No. |
2 |
|
|
Electrical Parameters |
Power Supply |
V/Ph/Hz |
220/1/50 |
|
|
Power Input |
W |
74 |
76 |
123 |
|
|
Current |
A |
0.32 |
0.33 |
0.54 |
|
|
Sound
Pressure |
H |
dB(A) |
45.8 |
45.5 |
46.3 |
|
|
M |
42.5 |
41 |
39.5 |
|
|
L |
37.1 |
35.2 |
33.1 |
|
|
Shipping Weight |
kg |
26.5 |
27.2 |
32 |
|
|
Connecting
Pipe Size |
Inlet |
inch |
3/4 |
3/4 |
3/4 |
|
|
Outlet |
3/4 |
3/4 |
3/4 |
|
|
|
|
|
|
|
|
|
|
|
Capacities are based on the following
conditions: |
|
|
|
|
|
►Summer Condition: Inlet DB/WB Air
Temperature : 27°c / 19°c |
|
|
|
|
Inlet/ Outlet
Water Temperature: 7°c
/ 12°c |
|
|
|
|
►Winter Condition: Inlet Air Temperature :
20°c |
|
|
|
|
|
Inlet water
Temperature: 50°c |
|
|
|
|
►Altitude : Sea Level |
|
|
|
|
|
►Sound level is measured at 1 meter
distance from outlet. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|